§ 3-1.236. Permit Amounts for Cryogens.


Latest version.
  • Chapter 1, Table 105.6.11 of the 2016 California Fire Code is amended to read as follows:

    105.6.11 Cryogenic Fluids. An operational permit is required to produce, store, transport on site, use, handle or dispense cryogenic fluids in excess of the amounts listed in Chapter 1, Table 105.6.11.

    EXCEPTION: Permits are not required for vehicles equipped for and using cryogenic fluids as a fuel for propelling the vehicle or for refrigerating the lading.

    Table 105.6.11—Permit Amounts for Cryogens'

    Type of
    Cryogenic Fluid
    Inside
    Building
    Outside
    Building
    Corrosive Over 1 gallon Over 1 gallon
    Flammable Over 1 gallon 55 gallons
    Highly Toxic Over 1 gallon Over 1 gallon
    Nonflammable 55 gallons 55 gallons
    Oxidizer (including oxygen) 50 gallons 50 gallons

     

    See Chapter 1 of the 2016 California Fire Code.