§ 3-1.233. Storage of Portable LP-Gas Containers Awaiting Use, Resale, or Exchange.
Latest version.
Section 6109.12 of the 2016 California Fire Code is hereby amended to read as follows:
6
109.12 Separation from exits.
Containers stored inside or outside buildings accessible to the public shall be located
not less than ten (10) feet from any exit door or building opening, when only one
(1) exit is provided from the building or area, and not less than five (5) feet from
any exit door or building opening, when two (2) or more exits are provided from the
building or area.
Table 6109.12 of the 2016 California Fire Code is hereby amended to read as follows:
Quantity of LP-Gas Stored (Pounds)
Distances to a Building or Group of Buildings, Public Way, or Line of Property that
can be Built Upon (feet)