Modesto |
Code of Ordinances |
Title 3. PUBLIC SAFETY |
Chapter 1. ADOPTION OF THE CALIFORNIA FIRE CODE, 2016 EDITION |
Article 2. Amendments, Additions and Deletions to the 2016 California Fire Code |
§ 3-1.226. Storage and Dispensing of Flammable and Combustible Liquids On Farms and Construction Sites.
Section 5706 of the 2016 California Fire Code is hereby amended to read as follows:
5706.1. General. The capacity of temporary aboveground tanks containing Class I and Class II Liquids shall not exceed one thousand one hundred (1,100) gallons (4163.9 L). The capacity of permanent aboveground tanks containing Class I and II Liquids shall not exceed ten thousand (10,000) gallons (37,854 L). Temporary tanks of single-compartment design shall be constructed in accordance with Section 5706; permanent tanks shall be constructed in accordance with Chapter 57 of the 2016 California Fire Code.
(Ord. No. 3663-C.S., § 2, effective 1-6-2017)